Fantech
ProductsFansBy Mounting TypeBeta Series – AD634V
Beta Series – AD634V
Download CatalogueAutocadPrint Friendly Version
Beta Series

Performance Curve - AD634V

Description

The Alpha & Beta Series of axial roof units are designed for a wide range of free intake and ducted exhaust air installations. These robust but lightweight exhaust units are available in 7 sizes in each range extending from 315 to 630mm diameter.
Features
  • Wide choice of speeds available.
  • All motors are speed-controllable.
  • Some 3-phase motors are 2-speed star/delta design.
  • Protective bird-mesh guards are fitted as standard on Alpha model unless fitted with optional shutters.
  • Shutters are fitted as standard to the Beta Series.
  • Robust, lightweight construction.
  • Can be used for free intake and ducted applications.
  • Can be mounted at angles up to 30o.
Construction

Cowls are of UV-stabilised plastic or fibreglass.
Impeller blades are GRP as standard with an option of aluminium where required.
Metal components have a corrosion-resistant finish.
Shutters are fitted as standard to the beta series and are an optional extra on the Alpha series.
A bird-mesh guard is fitted on the Alpha model unless fitted with optional shutters.

Motors

Type - Squirrel cage induction motors
Electricity supply - 230V, single or 415V, 3-phase, 50Hz
Bearings- sealed-for-life, ball
Speed-controllable using electronic or auto-transformer controllers

Internal Thermal Protection

Manual-reset thermal protection is supplied as standard on all motors.

Testing

Air flow testing to BS848:Part 1, 1980
Noise tests to BS848:Part 2, 1985

Special Note

Refer to Fantech for fan selections at speeds other than shown.
When shutters are fitted ensure the roof unit is mounted with the shutter hinge pointing down the slope of the roof. When shutters are fitted to the Alpha series derate performance by 15-20%.

Suggested Specification

The axial roof units shall be of the Beta Series as designed and manufactured by Fantech Pty Ltd.
The axial impellers shall be of GRP (unless specified otherwise) and driven by speed-controllable motors with Manual-reset thermal protection.
The impellers run in pressed steel plates ensuring a certifiable performance.
The windband shall be of the vertical discharge type, incorporating butterfly shutters as standard and constructed from fibreglass or galvanised steel. Steel components shall be corrosion protected.
All models shall be fully tested to BS848:Part1, 1980 for air flow and BS848:Part 2, 1985 for noise.

Technical Data - AD634V

Speed [rps]Avg. dBA @ 3mkWatts (Input)AmpsMax.°CApprox. Weight [kg]
22661.54.37052

Sound Data

Type631252505001K2K4K8K
Inlet8182868480787772

Dimensions

Dimension Drawing
ABCD
78010085700

*All dimensions in mm, unless otherwise stated

Wiring Diagram

Wiring Diagram

Diagram shown is for single-speed only.
For 2-speed and special motors, contact Fantech for details.

Ancillaries

Ancillary Image
SD1-S
Star/Delta Switch